PURMO International
Trench convectors

Aquilo FMK

Trench convectors - Aquilo FMK

Trench convectors Aquilo FMK are especially designed for the in-floor mounting. The heating element is a copper-aluminum heat exchanger, painted black, mounted inside a double-side galvanized steel duct, also painted black from the inside. From the top the convector is protected with a crosswise or lengthwise masking grille made of any material available in the Manufacturer’s offer, to be ordered separately. The exchanger’s connection to the heating system is executed with two stub pipes with a G ½” internal thread.

+

Technical specifications:

Width: 180, 260, 290, 340,420 mm
Length: from 1000 up to 3500mm
Height: 90, 110, 140 mm
Exchanger composition: aluminum finned copper pipes
Duct composition: as standard double- side galvanized steel sheet, black RAL 9005 dry powder- coated from the inside
option: stainless steel
Grille material: wood (oak, beech)
duralumin in colours of choice: natural, golden, light brown, dark brown or black
Connections: 2 x G ½"- internal thread 
Operating pressure: 10 bar
Max. temperature 110oC
Test pressure: 13 bar
Exchanger accessories: manual air vent, 2 exchanger side covers, a 10 cm long stainless steel flexible connectors kit with a G ½” thread
Duct accessories: leveling bolts M8x30 mm with internal hexagon (for the duct length up to 2.5 m – 4 pcs., over 2.5 m – 6 pcs.), 4 surface mounting elements with duct fixing screws, breakable pass for the hydronic heating system connection + 2 rubber passes for domestic electric circuit connection, steel metal sheet cover masking the exchanger connectors, protecting the exchanger and duct against damage or smudging during mounting, as well as protecting the duct against distortion during covering with concrete
  1. Roll-up crosswise grille (beech or oiled oak, raw or varnished, duralumin, stainless steel), or lengthwise grille (duralumin, stainless steel).
  2. Note: lengthwise grilles as shown on the picture require additional reinforced crossbars
  3. Option: L or Z-type fi nishing frame (only for PML and PMZ grilles). Not applicable for PMO grilles. Note: Z-type frame is shown on the picture.
  4. Convection metal sheet (for the increased heat effi ciency and the safety of use).
  5. Heat exchanger (copper pipes, aluminum fi ns, overall coated with black varnish).
  6. Metal sheet cover masking the connection to the domestic hydronic heating system.
  7. Convector’s duct (double-side galvanized, varnished metal sheet).
  8. Air vent.
  9. Surface mounting elements.
  10. Passes for the hydronic heating system connection (breakable).

Radiators sizes

Type 90

Type 110

Type 140

side views

top view - examples

Lc - convector’s overall length
L - exchanger’s length
B - width

Heat outputs and dimensions

Convectors’ heat output [W] in accordance with PN-EN 442 standard for parameters 75/65/20°C and 70/55/20°C:

  height (mm) 90 110 140
overall length (mm) width (mm) 180 260 290 340 420 180 260 290 340 420 180 260 290 340 420
1000 75/65°C 173 226 232 299 376 199 266 296 353 432 219 328 361 457 537

70/55°C 137 178 183 236 297 157 210 233 278 341 173 259 285 360 423
1100 75/65°C 196 256 263 338 426 225 301 335 399 489 248 371 408 517 607

70/55°C 155 202 207 267 336 178 238 264 315 386 195 293 322 407 479
1200 75/65°C 219 285 293 378 476 251 336 374 446 546 277 414 456 577 678

70/55°C 173 225 231 298 375 198 265 295 352 431 218 327 360 455 535
1300 75/65°C 242 315 324 417 525 278 371 413 492 603 305 458 503 637 749

70/55°C 191 248 255 329 414 219 293 326 388 476 241 361 397 502 590
1400 75/65°C 264 345 354 456 575 304 406 452 539 660 334 501 551 697 819

70/55°C 209 272 279 360 453 240 320 356 425 521 264 395 434 550 646
1500 75/65°C 287 374 385 496 624 330 441 491 585 717 363 544 598 757 890

70/55°C 227 295 303 391 492 260 348 387 461 565 286 429 472 597 702
1700 75/65°C 333 434 446 574 723 382 512 569 678 831 421 630 693 877 1031

70/55°C 262 342 351 453 570 301 403 448 535 655 332 497 547 692 813
1900 75/65°C 378 493 507 653 822 435 582 647 771 945 478 717 788 997 1172

70/55°C 298 389 400 515 648 343 459 510 608 745 377 565 622 787 924
2100 75/65°C 424 553 568 732 921 487 652 724 864 1058 536 803 883 1118 1313

70/55°C 334 436 448 577 727 384 514 571 681 835 423 633 697 881 1036
2300 75/65°C 470 612 629 810 1020 539 722 802 957 1172 594 889 978 1238 1455

70/55°C 370 483 496 639 805 425 569 633 754 924 468 701 771 976 1147
2500 75/65°C 515 672 690 889 1120 592 792 880 1049 1286 651 976 1073 1358 1596

70/55°C 406 530 544 701 883 467 624 694 828 1014 514 769 846 1071 1258
2700 75/65°C 561 731 751 968 1219 644 862 958 1142 1400 709 1062 1168 1478 1737

70/55°C 442 576 592 763 961 508 680 756 901 1104 559 837 921 1166 1370
2900 75/65°C 606 790 812 1046 1318 697 932 1036 1235 1514 767 1148 1263 1598 1878

70/55°C 478 623 640 825 1039 549 735 817 974 1194 604 906 996 1260 1481
3100 75/65°C 652 850 873 1125 1417 749 1002 1114 1328 1628 824 1235 1358 1719 2020

70/55°C 514 670 688 887 1117 591 790 878 1047 1283 650 974 1071 1355 1593
3300 75/65°C 698 909 934 1204 1516 801 1072 1192 1421 1741 882 1321 1453 1839 2161

70/55°C 550 717 737 949 1195 632 845 940 1120 1373 695 1042 1146 1450 1704
3500 75/65°C 743 969 995 1282 1615 854 1142 1270 1514 1855 939 1407 1548 1959 2302

70/55°C 586 764 785 1011 1273 673 901 1001 1194 1463 741 1110 1221 1545 1815

All Aquilo convectors available on request.

Types of connections

Water capacity and weight

Weight and water volume

width – B [mm] 180 260 290 340 420
height [mm] 90 110 140 90 110 140 90 110 140 90 110 140 90 110 140
weight [kg/m] 5.9 6.1 7.8 6.4 6.7 8.4 6.9 7.1 8.8 8.0 8.3 10.8 9.9 10.2 14.1
water volume [l/m] 0.3 0.3 0.7 0.3 0.3 0.7 0.3 0.3 0.7 0.4 0.4 1.0 0.7 0.7 1.4

Means of order

Convectors

*) non-standard convectors are the ones whose dimensions differ from the ones listed in the catalogue hereby

Note:
F1T - available width only 260, 290, 340 mm (height – 90 or 140 mm)
F1P - available width only 180 or 260 mm (height – only 90 mm, length – only up to 3000 mm)

Non-standard versions available at request.
The order execution proceeds only after the graphic design has been accepted by the Client.

Grilles

In places where intense mechanical load on the grilles might occur (car dealers, gyms), the duralumin or stainless steel grilles are recommended.

The moisture content for beech or raw oak Aquilo convector grilles is approx. 10%. To enable the Clients coloring of their own choice, the grilles are not sold protected by preliminary varnishing.

However, while stored or after mounting, raw wood grilles can naturally lengthen even with 2-3 mm per each meter of the grille’s length, due to the natural process of moisture absorption from the ambient air. To avoid the adverse effects of this natural process, the grilles need to be protected against moisture. Painting with oil or varnishing eliminates the possibility of the negative effects of swelling or shrinking of the wooden grilles. In case grilles become moist, they should be varnished only after they become entirely dry and return to their required length, appropriate to the duct’s dimensions.

Note:
All Aquilo convectors if you need to apply them in swimming pools must be ordered in special version. This applies to a special version of stainless steel duct as well as other specially designed pieces of equipment. In the description of the type of heater and pool grille version should be added to the type of letter B. Eg: FMKB, F1TB, F1PB or PMOB, PMLB, PMZB and further details as to the basic version. Recommended performance grille for the version pool of duralumin.

Hydraulic characteristics

Hydraulic characteristics for Aquilo FMK

Mass water flow (kg/h)

  1. FMK-18-LLL-09, FMK-18-LLL-11
  2. FMK-26-LLL-09, FMK-26-LLL-11
  3. FMK-29-LLL-09, FMK-29-LLL-11
  4. F1T-26-LLL-09

Mass water flow (kg/h)

  1. FMK-34-LLL-09, FMK-34-LLL-11
  2. F1T-29-LLL-09

Mass water flow (kg/h)

  1. FMK-42-LLL-09, FMK-42-LLL-11
  2. F1T-34-LLL-09
  3. FMK-18-LLL-14, FMK-29-LLL-14
  4. FMK-26-LLL-14, FMK-26-LLL-14

Mass water flow (kg/h)

  1. FMK-34-LLL-14
  2. F1T-29-LLL-14

Mass water flow (kg/h)

  1. FMK-42-LLL-14
  2. F1T-34-LLL-14

Accessories

Masking grilles

wooden, crosswise

Beech or oak
Raw, oiled or varnished
Roll-up crosswise grille with oak or beech crosspieces
The wooden grille is supplied, as standard, in the PMO raw version, i.e. with no fi nishing frame
Free fl ow: 58%

duralumin, crosswise

Roll-up crosswise grille with eloxed duralumin crosspieces
Available colors: natural, golden, light brown, dark brown or black
The grille is supplied, as standard, in the PMO raw version, i.e. with no fi nishing frame
Free fl ow: 71%

duralumin, lengthwise

Lengthwise grille with eloxed duralumin crosspieces
Available colors: natural, golden, light brown, dark brown or black
The grille is supplied, as standard, in the PMO raw version, i.e. with no fi nishing frame
Free fl ow: 71%

stainless steel, crosswise

Roll-up crosswise grille with stainless steel crosspieces
Steel variety: 1.4301
The grille is supplied, as standard, in the PMO raw version, i.e. with no fi nishing frame
Free fl ow: 58%

stainless steel, lengthwise

Lengthwise grille with stainless steel crosspieces
Steel variety: 1.4301
The grille is supplied, as standard, in the PMO raw version, i.e. with no fi nishing frame
Free fl ow: 58%

Accessories

DN15 thermostatic valve – NF shortened version:xxx

PN10 / 110 °C
Straight version DN15 PTV-01
Angle version DN15 PTV-02

DN15 thermostatic cut-off valve:

PN10 / 110 °C
Straight version DN15 PRS-01
Angle version DN15 PRS-02

PTH-01 thermostatic valve with a capillary pipe:

Temperature regulation control 8-28 °C
Capillary pipe’s length 2 m
Anti-freezing protection 8 °C

PPT-01 room thermostat:

Operating voltage 230 V / 50 Hz
Required temperature setting range 8 - 30 °C
Terminal load 0.2-6 (2) A
IP protection rating IP 30
Colour white RAL 9010
Width x height x depth 96.4 x 99.6 x 42.8 mm

Note: the thermostat should be positioned approx. 1.5 m above the fl oor level, and not exposed to direct sun radiation or other local heat or cold source.

PTP-02 actuator for thermostatic valve:

Operating voltage 230 V / 50 Hz no-current shut-off version
Cable length 1.2 m
Power load 2.5 W
Starting current (transitory) 250 mA (230 V / 50 Hz)
Connecting cable 2 x 0.75 mm2
IP protection rating IP 41 (horizontal mounting), IP 43 (mounting: vertical and ± 45° from the vertical axis)
Thread connector M30 x 1.5

PSP-01 manual 3-level rotation switch:

Operating voltage 230 V / 50 Hz
Number of rotation settings off + 3
Terminal load 0.2-6 (2) A
IP protection rating IP 30
Colour white RAL 9010
Width x height x depth 96.4 x 113.1 x 42 mm

PPT-02 room thermostat with a 3-level rotation switch:

Operating voltage 230 V / 50 Hz
Required temperature setting range 8 - 30 °C
Number of rotation settings off + 3
Terminal load 0.2-6 (2) A
IP protection rating IP 30
Colour white RAL 9010
Width x height x depth 96.4 x 113.1 x 42 mm

Note: the thermostat should be positioned approx. 1.5 m above the fl oor level, and not exposed to direct sun radiation or other local heat or cold source.

PER-05 room thermostat with automatic rotation switch - available option: remote control

Operating voltage 230 V / 50 Hz
Power load max 8 W
Control output load 230 V / 50 Hz, max 4 (2) A
IP protection rating IP 30
Required temperature setting range 5 - 40 °C
Fan rotation regulation manual (0,1,2,3) / automatic
Width x height x depth 86 x 86 x 39 mm

Note: the thermostat should be positioned approx. 1.5 m above the fl oor level, and not exposed to direct sun radiation or other local heat or cold source.

Note: order together with PER-06-IK fl ush box

PER-06 room thermostat with automatic rotation switch and weekly programming – available option: remote control

Operating voltage 230 V / 50 Hz
Power load max 8 W
Control output load 230 V / 50 Hz, max 4 (2) A
IP protection rating IP 30
Required temperature setting range 5 - 40 °C
Fan rotation regulation manual (0,1,2,3) / automatic
Width x height x depth 86 x 86 x 39 mm

Note: the thermostat should be positioned approx. 1.5 m above the fl oor level, and not exposed to direct sun radiation or other local heat or cold source.

Note: order together with PER-06-IK fl ush box

PER-06-IK fl ush box

for PER-05 and PER-06.

PER-05-DO remote control

for PER-05 and PER-06.

QAA-32 wall-mounted temperature sensor

Temperature measuring range 0 - 40 °С
Measuring accuracy at 25 °С ±0.3K
Time constant 6 min
Electrical connections
IP protection rating IP30
Width x height x depth 97 x 100x36 mm

QAH-11 clip-on temperature sensor with NTC resistance measuring element for the equipment with heating and/or cooling function

Temperature measuring range - 20… .+ 70 °С
Measuring accuracy at 25 °С ±0.3K
Time constant 1.5 min

PAT transformer ~230/12 V 50 Hz

version for surface mounting / power [W]
PAT-01-M-01 / 45
PAT-02-M-01 / 90
PAT-04-M-01 / 160
PAT-06-M-01 / 300

version for fl ush mounting / power [W]
PAT-01-M-02 / 45
PAT-02-M-02 / 90
PAT-04-M-02 / 160
PAT-06-M-02 / 300

Corrective factors

supply
water temperature
[˚C ]
air temperature
[˚C ]
Aquilo FMK trench convector n = 1.4
return water temperature [˚C ]


35 40 45 50 55 60 65 70 75 80 85




90 15 0.78 0.88 0.98 1.08 1.17 1.26 1.35 1.43 1.52 1.61 1.69
0.52 0.46 15 45
20 0.63 0.73 0.83 0.93 1.02 1.11 1.19 1.28 1.36 1.45 1.53
0.42 0.36 20
24 0.51 0.62 0.72 0.81 0.90 0.99 1.08 1.16 1.24 1.32 1.40
0.33 0.28 24
85 15 0.73 0.83 0.93 1.02 1.11 1.19 1.28 1.36 1.45 1.53
0.62 0.57 0.51 15 50
20 0.59 0.69 0.78 0.87 0.96 1.05 1.13 1.21 1.29 1.37
0.52 0.46 0.40 20
24 0.47 0.58 0.67 0.76 0.85 0.93 1.01 1.09 1.17 1.25
0.44 0.38 0.32 24
80 15 0.69 0.78 0.87 0.96 1.05 1.13 1.21 1.29 1.37
0.73 0.67 0.61 0.56 15 55
20 0.55 0.64 0.73 0.82 0.90 0.99 1.07 1.14 1.22
0.62 0.57 0.51 0.44 20
24 0.44 0.54 0.63 0.71 0.79 0.87 0.95 1.03 1.10
0.54 0.48 0.42 0.35 24
75 15 0.64 0.73 0.82 0.90 0.99 1.07 1.14 1.22
0.84 0.78 0.72 0.66 0.59 15 60
20 0.51 0.60 0.69 0.77 0.85 0.92 1.00 1.07
0.73 0.67 0.61 0.55 0.48 20
24 0.40 0.50 0.58 0.66 0.74 0.82 0.89 0.96
0.64 0.59 0.53 0.46 0.39 24
70 15 0.60 0.69 0.77 0.85 0.92 1.00 1.07
0.95 0.89 0.83 0.77 0.70 0.63 15 65
20 0.47 0.56 0.64 0.71 0.79 0.86 0.93
0.84 0.78 0.72 0.66 0.59 0.52 20
24 0.37 0.46 0.54 0.61 0.68 0.76 0.83
0.75 0.69 0.63 0.57 0.50 0.42 24
65 15 0.56 0.64 0.71 0.79 0.86 0.93
1.06 1.00 0.94 0.88 0.81 0.74 0.67 15 70
20 0.43 0.51 0.59 0.66 0.73 0.80
0.95 0.89 0.83 0.77 0.70 0.63 0.55 20
24 0.33 0.41 0.49 0.56 0.63 0.70
0.86 0.80 0.74 0.68 0.61 0.54 0.46 24
60 15 0.51 0.59 0.66 0.73 0.80
1.17 1.11 1.05 0.99 0.92 0.86 0.78 0.71 15 75
20 0.39 0.47 0.54 0.60 0.67
1.06 1.00 0.94 0.88 0.81 0.74 0.67 0.59 20
24 0.30 0.37 0.44 0.51 0.57
0.97 0.91 0.85 0.79 0.72 0.65 0.58 0.49 24
55 15 0.47 0.54 0.60 0.67
1.28 1.22 1.16 1.10 1.04 0.97 0.90 0.83 0.76 15 80
20 0.35 0.42 0.49 0.55
1.17 1.11 1.05 0.99 0.92 0.86 0.78 0.71 0.62 20
24 0.27 0.33 0.40 0.46
1.08 1.02 0.96 0.90 0.83 0.77 0.69 0.61 0.52 24
50 15 0.42 0.49 0.55
1.40 1.34 1.28 1.21 1.15 1.08 1.01 0.94 0.87 0.79 15 85
20 0.31 0.37 0.43
1.28 1.22 1.16 1.10 1.04 0.97 0.90 0.83 0.75 0.66 20
24 0.23 0.29 0.35
1.19 1.13 1.07 1.01 0.95 0.88 0.81 0.73 0.66 0.56 24
45 15 0.37 0.43
1.51 1.45 1.39 1.33 1.26 1.19 1.13 1.06 0.98 0.91 0.82 15 90
20 0.27 0.33
1.40 1.34 1.28 1.21 1.15 1.08 1.01 0.94 0.87 0.78 0.69 20
24 0.19 0.25
1.30 1.25 1.19 1.12 1.06 0.99 0.92 0.85 0.77 0.68 0.59 24





85 80 75 70 65 60 55 50 45 40 35



return water temperature [˚C ] Aquilo F1T, F1P, F2C, F4C trench convectors, fan version n = 1.1 air temperature
[˚C ]
supply
water temperature [C]

Example: the FMK-26-100-11 convector, heat output at 75/65/20°C: QN = 266 W, supply temperature: 55°C, return temperature: 45°C, air temperature: 20°C, heat transfer coeffi cient K1 = 0.49 Calculated heat output: Q = QN x K1 = 266 W x 0.49 = 130 W

Technical catalogue - Aquilo convectors

Warranty terms and conditions for PURMO steel panel radiators

  1. PURMO panel radiators are marketed and made available pursuant to the Regulation (EU) of the European Parliament and of the European Council No. 305/2011 laying down harmonized conditions for the marketing of construction products.
  2. Rettig Heating Sp. z o.o. located in Rybnik at Przemysłowa street ( hereinafter referred to as the Guarantor) gives 10 years guarantee ( from date of purchase ) for PURMO panel radiators mounted in water installation of the central heating ,yet not longer than 11 years since the production date given on the radiator.
    10 years guarantee applies to radiators manufactured since 06.03.2007.
  3. The guarantee is valid for radiators mounted in the water installations of the central heating:
    • in closed system with an expansion tank;
    • powered from the heat centre, boiler house or heat pump; 
    • made from black steel / copper or plastic pipes with an antidiffusion barrier; 
    • equipped with local air vents  (no central vent system is allowed) ;
    • used for heating residential areas, office buildings , service stations  or other buildings  that are neither exposed on pernicious corrosive substance activity  nor permanent or temporary moistness of the radiator surface .
    Installation of Purmo panel radiators in small open system installations ( up to 25 kW) is allowed provided the corrosion inhibitors are used.
    During the warranty period the radiators and their components with the faults originated from the manufacturer and reported not later than one month after having been discovered will be repaired or exchanged into new, free of defects devices.
  4. The guarantee is recognized when:
    • there is an evidence of purchase, that is the invoice, 
    • the radiators have been mounted in water central heating systems in compliance with the national technical regulations and standards, 
    • adhering to the requirements of the Guarantor included in „ Terms and conditions of Purmo panel radiators usage”.
  5. Maximal operating pressure in central heating installation for PURMO panel radiators may not exceed 10 bars (6 bars for Vertical radiators ) and the maximal service temperature is 110 °C.
    In high and high-rise buildings a zone distribution system must be applied. The tightness test must be carried out at the experimental pressure equal to working pressure in the installation, adding two bars, yet not lower than four bars. Maximal pressure during the installation tightness test shall be equal to 12 bars ( 8 bars for Vertical radiators). 
  6. The guarantee does not cover radiators mounted:
    • in central heating installation connected to a high temperature heat distribution network through a suction elevator or  pump mixing loop;
    • in swimming pool areas, car wash centers, laundries, slaughterhouses, public toilets, bathrooms or other rooms with high activity of corrosive substances in the air , as well as areas where the radiator is exposed on  permanent or temporary moistness – it does not refer to galvanized radiators , with additional anti-corrosive protection and guarantee for 6 years , yet not longer than 7 years since the production date
    • in central heating installations connected with the water- supply system without protective fittings, against backflows; 
    • in central heating installation with water removed  more frequently or for longer periods than advised in exploitation requirements; 
    • in steam installations ;
    • in central heating installations where the water quality rating level has been higher than advised, that is :
    • the total amount of chloride and sulfate ions may not be higher than 150 mg/l ( for installations with copper pipes not higher than  50 mg/l ),
    • oxygen content not higher than 0.1 mg/l,
    • pH water reaction within 7.0 ÷ 9.5,
    • total water hardness not higher than  4.0 mval/l.
  7. The guarantee does not cover damages to the radiator or its parts ( brackets, covers) that are due to improper handling, storage, transport or misuse.
    It refers, in particular, to radiators:
    • stored in the open air before mounting,
    • with mechanical damage,
    • polluted from inside with solid bodies or noxious liquids, 
    • deformed by excessive experimental pressure or static pressure in the installation,deformed due to freezing,
    • with mechanical damage due to an overload as a result of sitting on the radiator.
  8. The radiators must be mounted with the original packaging. The packaging must be left on the radiator even if the central heating installation is activated for heating in buildings during finishing works or for drainage purposes. It is recommended to remove the packaging after accomplishing all finishing works.
    The radiators require periodical cleaning. It is recommended to use only soft and gentle fabrics that can be slightly moistened.  For cleaning the radiators it is not advised to use aggressive or corrosive agents ( e.g. acidic solvents or agents with chlorine). Panel radiators cannot be used for drying wet or dump objects put on the radiator. Claims for damage of varnished surfaces to improper handling or maintenance will not be granted. 
  9. It is forbidden to remove the water from the entire installation or its part and to leave it in this condition. It also refers to new installations with the tightness test. If there is a need to remove the water , e.g. due to renovation or maintenance works, the water must be removed only from the given part. After accomplishing all works the installation must immediately be filled with water. Quantity of water used for the filling or filling up process must be monitored, e.g. by a watermeter.
  10. The guarantee of our product is granted provided it has not been repaired or modified by a buyer or third party without Guarantor’s approval. 
  11. Occurrence of faults within the warranty period is followed by a claim procedure by notifying the Retailer about the damage in a special claim form including the origin and details of damage. The retailer accepts the claim form and forwards it to the Guarantor via registered letter, fax or e-mail within 24 hours since it has been accepted. In case of incomplete data , the form shall be returned in order to be completed. The invoice or its copy shall be attached with the form. In specific cases the Guarantor may request a photo documentation of the claimed product. The Guarantor is obliged to reply for the complaint in writing within 14 days since a completed form was accepted. 
  12. In order to recognize the claim a visual inspection is performed by the Guarantor in the mounting area or other area determined by the Guarantor. The original packaging used for delivery must be kept for the inspection in case of a damage with mechanical origin. If the claim has been recognized , the Guarantor is obliged to repair or replace the parts found to be defective due to improper manufacturing or material defects or exchange the radiator into a new device that is free of defects. In specific cases,  ( e.g. when the product needs to be sent from abroad) the Guarantor has the right to extend the deadline to recognize the claim that is normally defined to be 14 days.
    In case of damages that do not affect the radiator functionality, a discount may also be offered.
    In case of the claim regarding a product, manufacturing of which has been ceased , the Guarantor will offer an equivalent with similar  parameters or a money back guarantee at the date of the purchase. The Guarantor does not deliver an alternative device for the time of claim recognition process.
  13. The Guarantor has the right to select the method of claim settlement.
    In case the claim is recognized in the form of exchange, all mounting shall be delivered by an authorized Purmo service centre. In case any difficulties occur when mounting the exchanged radiator, e.g. lack of valve for separating the radiator from installation, the service centre may refuse to disassemble or mount the new radiator. As a consequence, the warranty claim is recognized as exercised by the Guarantor.
  14. The warranty period shall be extended due to reparation time calculated since the date of delivery to the Guarantor to the reparation date . In case of exchange a new warranty period is granted.
  15. The Guarantor reserves the right to make modifications to his products without prior notice unless they refer to any significant technical details affecting the process of selection. 
  16. The warranty terms on goods sold do not exclude , limit or suspend  rights of the buyers when the product fails to comply with the contract in accordance with the Act of 27.07. 2002 on specific conditions of consumer sale and amendings of  the Civil Code. (Journal of Laws  2002  no. 141, point 1176).
  17. Warranty conditions are valid as stated since  01.07.2013 .